"All prices are subject to change without prior notice due to currency fluctuation Please confirm prices before placing the order to avoid any confusion"
PREORDER Fluke 1555FC Insulation Tester 10kV

Fluke 1555FC

Key features

·         Quickly configure, start and stop tests on the 1555 remotely, a safe distance away from any operating, energized equipment, using Fluke Connect® and a smart phone

·         Real time trending gives you easy-to-see visual cues, rather than hard to read, rapidly changing values

·         Report creation using Fluke Connect desktop saves time and makes test results easier to understand

·         Fluke Connect saves test results to the cloud for analysis and preventive maintenance

Product overview: Fluke 1555 FC 10 kV Insulation Tester

Perform tests, collect data wirelessly and from a safe distance

The Fluke 1555 insulation resistance tester offers digital insulation testing up to 10 kV, making it ideal for testing high voltage equipment including switchgear, motors, generators and cables.

Data collection is easy using the Fluke Connect® wireless app. Remote operation lets you spend as little time as possible in potentially hazardous zones. Real-time trending shows a live graph on your phone, rather than a hard-to-read set of changing values. And you can create reports quickly, using pre-designed templates that you can customize with company logos. The 1555 insulation tester can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, CAT IV 600 V safety rating.

Other useful features:

  • Automatic calculation of Dielectric Absorption (DAR) and Polarization Index (PI) with no additional setup
  • Guard system eliminates the effect of surface leakage current on high-resistance measurements
  • Selectable test voltages in 50 V steps from 250 V to 1000 V, and 100 V steps above 1000 V
  • CAT III 1000 V, CAT IV 600 V safety rating
  • Warning function alerts the user that line voltage is present and gives the voltage reading up to 600 V AC or DC for increased user safety
  • Measurements can be stored in up to 99 memory locations, with each location assigned a unique, user defined, label for easy recall
  • Long battery life gives the user over 750 tests between charges
  • Large digital/analog LCD for easy viewing
  • Capacitance and leakage current measurement
  • Ramp function for breakdown testing
  • Resistance measurements up to 2 TΩ
  • Timer settings up to 99 minutes for timed tests

 

 

 

Specifications: Fluke 1555 FC 10 kV Insulation Tester

Electrical Specifications

The tester's accuracy is specified for one year after calibration at operating temperatures of 0°C to 35°C. For operating temperatures outside the range (-20°C to 0°C and 35°C to 50°C), add ±.25% per °C, except on the 20% bands add ±1% per °C.

Insulation Resistance Measurement

Test voltage (DC)

250 V

Range

< 250 kΩ,
250 kΩ to 5 GΩ
5 GΩ to 50 GΩ
> 50 GΩ

Accuracy (± reading)

Unspecified
5%
20%
Unspecified

500 V

Range

< 500 kΩ
500 kΩ to 10 GΩ
10 GΩ to 100 GΩ
> 100 GΩ

Accuracy (± reading)

Unspecified
5%
20%
Unspecified

1000 V

Range

< 1 MΩ
1 MΩ to 20 GΩ
20 GΩ to 200 GΩ
> 200 GΩ

Accuracy (± reading)

Unspecified
5%
20%
Unspecified

2500 V

Range

< 2.5 MΩ
2.5 MΩ to 50 GΩ
50 GΩ to 500 GΩ
> 500 GΩ

Accuracy (± reading)

Unspecified
5%
20%
Unspecified

5000 V

Range

< 5 MΩ
5 MΩ to 100 GΩ
100 GΩ to 1 TΩ
> 1 TΩ

Accuracy (± reading)

Unspecified
5%
20%
Unspecified

10000 V

Range

< 10 MΩ
10 MΩ to 200 GΩ
200 GΩ to 2 TΩ
> 2 TΩ

Accuracy (± reading)

Unspecified
5%
20%
Unspecified

Bar graph range

0 to 1 TΩ (1550C) - 0 to 2 TΩ (1555)

Insulation test voltage accuracy

-0%, +10% at 1 mA load current

Induced AC mains current rejection

2 mA maximum

Charging rate for capacitive load

5 seconds per μF

Discharge rate for capacitive load

1.5 s/μF

Leakage current measurement

Range

1 nA to 2 mA

Accuracy

±(5% + 2 nA)

Capacitance measurement

Range

0.01 μF to 15.00 μF

Accuracy

±(15% rdg + 0.03 μF)

Timer

Range

0 to 99 minutes

Resolution setting

1 minute

Resolution indication

1 second

Live circuit warning

Warning range

30 V to 660 V AC/DC, 50/60 Hz

Voltage accuracy

±(15% + 2 V)

Software specifications

FlukeView Forms™ basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8.

General Specifications

Display

75 x 105 mm

Power

12 V lead-acid rechargeable battery, Yuasa NP2.8-12

Charger Input (AC)

85 V to 250 V AC 50/60 Hz 20 VA

This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord. The protective earth terminal (ground pin) is not connected internally. The extra pin is for added plug retention only.

Dimensions

269 x 277 x 160 mm (10.6 x 10.9 x 6.3 in)

Weight

3.7 kg (8.2 lb)

Temperature (operating)

-20°C to 50°C (-4°F to 122°F)

Temperature (storage)

-20°C to 65°C (-4°F to 149°F)

Humidity

80% to 31°C decreasing linearly to 50% at 50°C

Altitude

2000 m

Enclosure sealing

IP40

Input overload protection

1000 V AC

Electromagnetic compatibility

EN 61326

Safety compliance

IEC 61010-1: Overvoltage category II, Pollution Degree 2.
IEC 61010-2-030: Measurement 600V CAT IV / 1000V CAT III
IEC 61557-1, IEC 61557-2

 


Fluke 1555FC

  • Views: 1770
  • Product: Insulation Tester 10kV
  • Availability: PREORDER
  • Rs 0
  • Free Shipping
whatsapp

Tags: fluke, 1555fc, pre, orders insulation, tester, 10kv digital, 5000v