Fluke 117C
Key features
- Accurate,
easy-to-use multimeter with integrated VoltAlert™ technology for
non-contact voltage detection
- Features
AutoVolt automatic AC/DC voltage selection
- Provides
low input impedance to help prevent false readings due to ghost voltage
- Presents
a large white LED backlight for working in poorly lit areas
- Features
True RMS capabilities for accurate measurements on non-linear loads
Product overview: Fluke 117 Electrician's Ideal Multimeter with Non-Contact
Voltage
The Fluke 117 Digital Multimeter includes integrated
non-contact voltage detection to help get the job done faster
Designed by electricians and engineered by Fluke, the Fluke
117 is a compact True-RMS meter for demanding applications like commercial
buildings, hospitals, and schools. With its integrated non-contact voltage
detection, Auto Volts and LoZ functions that help prevent false readings caused
by ghost voltage, the Fluke 117 is a great choice for electricians. In fact,
users around the world have said their 117 is an investment in accuracy. The
Fluke 117 provides Min/Max/Average readings and measures frequency and
capacitance. Plus, its easy-to-use interface can save you time and enable you
to move from job to job more quickly.
Engineered and Tested with Your Safety on the Job in Mind
We test Fluke 117 multimeters for safe use in CAT III 600 V
environments and we have designed in several features to make it easier and
faster for you to get the measurements you need, including:
- Measures
10 A (20 A overload for 30-seconds)
- Measures
resistance, continuity, frequency, and capacitance
- Provides
Min/Max/Average to record signal fluctuations
- Comes
with an holster with probe holders for easy storage
- Features
compact ergonomic design for one-handed operation
- Fits
into optional ToolPak™ magnetic hanger for hands-free operation
- CAT
III 600 V safety rated
- A
large white LED backlight to improve measurement visibility in poorly lit
areas
- VoltAlert™
technology for fast, go/no go non-contact voltage detection
- AutoVolt
and low input impedance modes to provide faster, more accurate readings
- Specifications:
Fluke 117C Multimeter with Non-Contact Voltage
Specifications |
||||||
Maximum
voltage between any terminal and earth ground |
600 V |
|||||
Surge
protection |
6 kV
peak per IEC 61010–1 600 VCAT III, Pollution Degree 2 |
|||||
Fuse
for A input |
11 A,
1000 V FAST Fuse (Fluke PN 803293) |
|||||
Display |
Digital:
6,000 counts, updates 4 per second |
|||||
Bar
graph |
33
segments, updates 32 per second |
|||||
Operating
temperature |
-10°C
to +50°C |
|||||
Storage
temperature |
-40°C
to +60°C |
|||||
Battery
type |
9 volt
Alkaline, NEDA 1604A / IEC 6LR61 |
|||||
Battery
life |
400
hours typical, without backlight |
|||||
Accuracy
Specifications |
||||||
DC
millivolts |
Range/resolution |
600.0
mV / 0.1 mV |
||||
Accuracy |
±([% of
reading] + [counts]): 0.5% + 2 |
|||||
DC
volts |
Range/resolution |
6.000 V
/ 0.001 V |
||||
Accuracy |
±([% of
reading] + [counts]): 0.5% + 2 |
|||||
Auto
volts |
Range/resolution |
600.0 V
/ 0.1 V |
||||
Accuracy |
2.0% +
3 (DC, 45 Hz to 500 Hz) |
|||||
AC
millivolts¹ True RMS |
Range/resolution |
600.0
mV / 0.1 mV |
||||
Accuracy |
1.0% +
3 (DC, 45 Hz to 500 Hz) |
|||||
AC
volts¹ True RMS |
Range/resolution |
6.000 V
/ 0.001 V |
||||
Accuracy |
1.0% +
3 (DC, 45 Hz to 500 Hz) |
|||||
Continuity |
Range/resolution |
600 Ω /
1 Ω |
||||
Accuracy |
Beeper
on < 20 Ω, off > 250 Ω detects opens or shorts of |
|||||
Ohms |
Range/resolution |
600.0 Ω
/ 0.1 Ω |
||||
Accuracy |
0.9% +
1 |
|||||
Range/resolution |
40.00
MΩ / 0.01 MΩ |
|||||
Accuracy |
5% + 2 |
|||||
Diode
test |
Range/resolution |
2.00 V
/ 0.001 V |
||||
Accuracy |
0.9% +
2 |
|||||
Capacitance |
Range/resolution |
1000 nF
/ 1 nF |
||||
Accuracy |
1.9% +
2 |
|||||
Range/resolution |
>
1000 μF |
|||||
Accuracy |
5% +
20% |
|||||
Lo-Z
capacitance |
Range |
1 nF to
500 μF |
||||
Accuracy |
10% + 2
typical |
|||||
AC amps
True RMS (45 Hz to 500 Hz) |
Range/resolution |
6.000 A
/ 0.001 A |
||||
Accuracy |
1.5% +
3 |
|||||
DC amps |
Range/resolution |
6.000 A
/ 0.001 A 10.00 A / 0.01 A |
||||
Accuracy |
1.0% +
3 |
|||||
Hz (V
or A input)² |
Range/resolution |
99.99
Hz / 0.01 Hz |
||||
Accuracy |
0.1% +
2 |
|||||
1. All
AC voltage ranges except Auto-V/LoZ are specified from 1% to 100% of range.
Auto-V/LoZ is specified from 0.0 V. |
||||||
Mechanical
and General Specifications |
||||||
Size |
167 x
84 x 46 mm (6.57 x 3.31 x 1.82 in) |
|||||