Main Menu / Categories
Your Cart

KEW5050 KYORITSU Price In Pakistan

Buy Now KEW5050 KYORITSU At Best Price In Pakistan 2025.

Unpreceded Ior Logger!

  • Provides simultaneous measurements and logs up to 4 channels
  • Supports various wiring systems
    (Single-phase 2&3-wire, Three-phase 3&4-wire*) *Except Ior for 3 Phase 4 wire
  • World's fastest class speed at 200ms interval for leakage current measurement
  • Offers both traditional leakage / load current measurements
  • Large graphic display and magnet on the back case to attach it on metal enclosures


  • Wiring configuration
  • 1P2W, 1P3W, 3P3W, 3P4W
  • Measurements and
    parameters
  • Ior : Leakage current (Trms) with resistive components only
    Io : Leakage current (Trms) with basic wave of 50/60Hz only
    Iom : Leakage current (Trms) including harmonic components
    V : Reference voltage (Trms) with basic wave of 50/60Hz only
    Vm : Reference voltage (Trms) including harmonic components
    R : Insulation resistance, Frequency(Hz), Phase angle(θ)
  • Other functions
  • Digital output, Print screen, Backlight, Data hold
  • Recording Interval
  • 200/400ms/1/5/15/30s/1/5/15/30m/1/2hours
  • Ior
  • Range
  • 10.000/100.00/1000.0mA/10.000A/AUTO
  • Accuracy
  • For reference voltages of sine wave 40 to 70Hz and 90V Trms or higher,
    ±0.2%rdg±0.2%f.s. + clamp sensor amplitude accuracy + error of phase accuracy*
    (phase error)
    * add ±2.0%rdg to measured Io value when using Ior leakage clamp sensor.
    (θ: within the accuracy of reference voltage/ current phase difference ±1.0°)
  • Allowable input
  • 1% to 110% (Trms) of each range, and 200% (peak) of the range
  • Display range
  • 0.15% to 130% (display “0” for less than 0.15%, “OL” if the range is exceeded)
  • Io *Range, Allowable input and Display Range are the same as Ior .
  • Accuracy
  • ±0.2%rdg±0.2%f.s.+ clamp sensor amplitude accuracy
  • Iom *Range, Allowable input and Display Range are the same as Ior .
  • Accuracy
  • ±0.2%rdg±0.2%f.s.+ clamp sensor amplitude accuracy
  • Measurement
    method
  • Sampling speed 40.96ksps (every 24.4μs), gapless, calculate Trms values every 200ms.
  • Voltage
  • Range
  • 1000.0V
  • Accuracy
  • ±0.2%rdg±0.2%f.s. * for waveforms of sine wave 40 to 70Hz
  • Allowable input
  • 10 to 1000V Trms, and 2000V peak
  • Display range
  • 0.9 to 1100.0V Trms (display “0” for less than 0.9V, “OL” if the range is exceeded)
  • Phase angle(θ)
  • Display range
  • 0.0 to ±180.0° (regarding the phase of reference voltage as 0.0°)
  • Accuracy
  • Within ±0.5° for the inputs of 10% or higher of leakage current range,
    sine wave 40 to 70Hz, reference voltage of 90V Trms or higher.
    Within ±1.0° when using Ior leakage clamp sensor, and
    Within ±0.5°+ clamp sensor accuracy when using general purpose clamp sensor.
  • Frequency meter range
  • 40 to 70Hz
  • External supply
  • AC100 to 240V(50/60Hz) 7.5VA max
  • Power source
  • LR6(AA)(1.5V) × 6 (Battery life approx. 11h)
  • Display / update period
  • 160 × 160dots, FSTN monochrome display / 500ms
  • PC card interface
  • SD card (2GB) *standard accessory
  • Communication
    interface
  • USB
  • Temperature and
    humidity range
  • 23±5°C, relative humidity 85% or less(no condensation)
  • Operating temperature
    and humidity range
  • -10 to 50°C, relative humidity 85% or less(no condensation)
  • Storage temperature
    and humidity range
  • -20 to 60°C, relative humidity 85% or less(no condensation)
  • Applicable Standards
  • IEC 61010-1 CAT 300V / CAT 600V Pollution degree 2
    IEC 61010-2-030, IEC 61010-031, IEC 61326
  • Dimension
  • 165(L) × 115(W) × 57(D)mm
  • Weight
  • Approx. 680g (including batteries)
  • Accessories
  • 7273 (Voltage test lead)
    8262 (AC adapter)
    7278 (Earth cable)
    7219 (USB cable)
    8326-02 (SD card [2GB])
    9125 (Carrying case)
    Instruction manual, Cable marker, LR6(AA) × 6
  • Optional Accessories