Main Menu / Categories
Your Cart

KEW3005A KYORITSU in Pakistan

Bar graph to display insulation resistance

  • Bar graph to display insulation resistance
  • Displays the value of external AC voltage with flashing symbol
  • Auto null function to automatically subtract the test lead resistance before displaying the real continuity resistance value
  • Live circuit warning buzzer
  • Releasing the test button automatically discharges the charges stored in the circuit under test
  • 200mA measuring current on continuity testing

    Specification
  • Insulation Resistance
  • Test voltage
  • 250/500/1000V
  • Measuring ranges
    (Mid-scale value)
  • 20/200/2000MΩ
  • Output voltage on open circuit
  • Rated test voltage
    +20%, -0%
  • Nominal current
  • 1mA DC min.
  • Output short circuit current
  • 1.5 mA DC approx.
  • Accuracy
  • ±1.5%rdg±5dgt (20/200MΩ)
    ±10%rdg±3dgt (2000MΩ)
  • Continuity Test
  • Measuring ranges
    (Mid-scale value)
  • 20/200/2000Ω
  • Output voltage on open circuit
  • 7 to 12V DC
  • Measuring current
  • 200mA DC min.
  • Accuracy
  • ±1.5%rdg±5dgt (20Ω)
    ±1.5%rdg±3dgt (200/2000Ω)
  • AC Voltage
  • AC voltage range
  • 0 to 600V AC
  • Accuracy
  • ±5%rdg±3dgt
  • General
  • Applicable standard
  • IEC 61010-1 CAT III 300V Pollution Degree 2
    IEC 61010-2-031, IEC 61010-2-034, IEC 61557-1,2,4
    IEC 60529 (IP54), IEC 61326-1 (EMC)
  • Power source
  • R6 (AA) (1.5V) × 8
  • Dimension
  • 167(L) × 185(W) × 89(D)mm
  • Weight
  • Approx. 970g