Seaward PV150
Seaward PV150
- Stock: Pre-Order
- Model: Seaward Solar PV150 Solarlink PV String Tester Kit
The Seaward PV150 Solar Installation Tester allows electrical safety and performance verification of photovoltaic installations in a safe and easy-to-use device.
Technical Specifications
Open Circuit Voltage Measurement (PV Terminals) | |
---|---|
Display Range | 0.0VDC - 1000VDC |
Measuring Range | 5.0VDC - 1000VDC |
Resolution | 0.1VDC maximum |
Accuracy | ± (0.5 % + 2 digits) |
Enunciators | DC voltage polarity correct or reversed |
Earth Continuity Resistance Measurement (4mm Terminals) | |
---|---|
Test Voltage Open Circuit | >4VDC, nominal |
Test Current into 2 Ω | >200mA |
Display Range | 0.00Ω - 199Ω |
Measuring Range (EN 61557-4) | 0.05Ω - 199Ω |
Resolution | 0.01Ω maximum |
Accuracy | ± (2% + 5 digits) |
Test Leads Zero | Zero up to 10Ω, by zero button |
Visible Warning | ≥30V AC or DC at inputs |
Circuitry Protection | Test inhibited if ≥30V AC or DC at inputs |
Repeat tests as per IEC61557-4 | Approx 4000 1 second test |
Rpe Voltage Measurement (4mm Terminals) | |
---|---|
Display Range | 30V - 440VAC/DC |
Voltage Measuring Range | 30V - 440VDC |
30V - 440VAC 50-60Hz | |
Resolution | 1V |
Accuracy | ± (5% + 2 digits) |
DC Operating Power (via AC/DC Current Clamp and PV Terminals) | |
---|---|
Display Range | 0.00kW - 40kW |
Measuring Range | 0.50kW - 40kW |
Resolution | 0.01kW |
Accuracy | ± (5% + 5 digits) |
Connectivity | |
---|---|
USB download to PC (CSV format) | |
Wireless “Solarlink TM” to Survey 200R (range ~30m/100ft) |
Short Circuit Current Measurement (PV Terminals) | |
---|---|
Display Range | 0.00ADC - 15.00ADC |
Measuring Range | 0.50ADC - 15.00ADC |
Maximum Power | 10kW |
Resolution | 0.01ADC maximum |
Accuracy | ± (1% + 2 digits) |
Insulation Resistance (Auto Test Sequence, PV Terminals and Red 4mm Terminal) | |
---|---|
Test Voltage Open Circuit | 250V, 500V, 1000V (as per IEC61557-2) |
Test Voltage Specification | -0% +20% (open circuit) |
Test Voltage @ 1mA | >1mA into UN x (1000Ω/V) |
Test Current Short Circuit | <2mA |
Display Range | 0.05MΩ - 199MΩ |
Measuring Range (EN 61557-2) | 0.05MΩ - 199MΩ |
Resolution | 0.01MΩ maximum |
Accuracy | 0.05MΩ - 100MΩ ± (5% + 5 digits) |
101MΩ - 199MΩ ± (10% + 5 digits) | |
Visible Warning | ≥ 30V AC or DC at inputs |
Circuitry Protection | Test inhibited if ≥ 30V AC or DC at inputs |
Repeat tests as per IEC61557-4 | Approx 3000 1 second tests |
Operating Current (via AC/DC Current Clamp) | |
---|---|
Display Range | 0.1A - 40.0A |
Current Measuring Range | 0.1A - 40.0A DC |
0.1A - 40.0A AC 50-60Hz | |
Resolution | 0.1A |
Accuracy | ± (5% + 2 digits) |
Instrument Dimensions and Weight | |
---|---|
Weight | 0.95kg / 2.1lb |
Dimensions | 26.4 x 10.7 x 5.8cm / 10.4 x 4.2 x 2.3” |
Display | Custom LCD with backlight |
Power Source | 6 x 1.5V AA cells |
Battery life | >1000 test sequences |
Auto power down | User programmable |
Onboard memory | Up to 200 complete test datasets |