FLUKE 1503
- Stock: In Stock
- Model: Insulation Resistance Meter
Key features
- A rugged, compact insulation resistance tester for residential and commercial electricians
- Performs insulation tests from 0.01 MΩ to 2000 MΩ
- Offers two insulation test voltages: 500 V and 1000 V
- Includes live circuit detection to prevent insulation test if voltage >30 V is detected
- Measures resistance from 0.01 Ω to 20.00 kΩ
Other useful capabilities:
- Measures AC/DC voltage from 0.1 V to 600 V
- Includes auto-discharge of capacitive voltage for added user protection
- Provides lo-ohms earth-bond continuity (200 mA)
- Simplifies repetitive or hard-to-reach testing with the remote test probe
- Saves battery power with auto power off
- Presents results on a large, backlit display
- Features CAT IV 600 V overvoltage category rating
- Comes with remote probe, test leads, test probes, alligator clips, and one-year warranty
- Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work
- Runs on four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests
Specifications: Fluke 1503 Insulation Resistance Meter
AC/DC Voltage Measurement |
|||
Accuracy |
Range |
600.0 V |
|
Resolution |
0.1 V |
||
50 Hz to 400 Hz ±(% of Rdg + Digits) |
±(2% + 3) |
||
Input impedance |
3 MΩ (nominal), < 100 pF |
||
Common mode rejection ratio (1 kΩ unbalanced) |
> 60 dB at DC, 50 or 60 Hz |
||
Overload protection |
600 V rms or DC |
||
Earth Bond Resistance Measurement |
|||
Range/Resolution |
20.00 Ω |
0.01 Ω |
|
200.0 Ω |
0.1 Ω |
||
2000 Ω |
1.0 Ω |
||
20.00 kΩ |
0.01 kΩ |
||
Accuracy |
±(1.5% + 3) |
||
Overload protection |
2 V rms or DC |
||
Open circuit test voltage |
> 4.0 V, < 8 V |
||
Short circuit current |
> 200.0 mA |
||
Insulation Specifications |
|||
Measurement range |
0.01 MΩ to 2000 MΩ |
||
Test voltage |
500 V, 1000 V |
||
Test voltage accuracy |
+ 20%, - 0% |
||
Short circuit current |
1 mA nominal |
||
Auto discharge |
Discharge time < 0.5 second for C = 1 µF or less |
||
Live circuit indicator |
Inhibit test if terminal voltage > 30 V prior to initialization of test |
||
Maximum capacitive load |
Operable with up to 1 µF load |
||
Measure accuracy |
|||
500 V |
±(1.5% + 5) |
||
1000 V |
±(1.5% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ |
||
General Specifications |
|||
Maximum voltage applied to any terminal: |
600 V AC rms or DC |
||
Storage temperature |
-40°C to 60°C (-40°F to 140°F) |
||
Operating temperature |
-20°C to 55°C (-4°F to 131°F) |
||
Temperature coefficient |
0.05 x (specified accuracy) per °C for temperatures < 18°C or > 28°C (< 64°F or > 82°F) |
||
Relative humidity |
|||
0% to 95% @ 10°C to 30°C (50°F to 86°F) |
|||
0% to 75% @ 30°C to 40°C (86°F to 104°F) |
|||
0% to 40% @ 40°C to 55°C (104°F to 131°F) |
|||
Vibration |
Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument |
||
Shock |
1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor) |
||
Electromagnetic compatibility |
In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997) |
||
Safety |
Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV) |
||
Certifications |
CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition |
||
Batteries |
Four AA batteries (NEDA 15A or IEC LR6) |
||
Battery llife |
Insulation test use: |
Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. |
|
Resistance measurements: |
Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 Ω with a duty cycle of 5 seconds on and 25 seconds off. |
||
Size (H x W x L) |
5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in) |
||
Weight |
550 g (1.2 lb) |
||
IP rating |
IP40 |
||
Altitude |
Operating |
2000 m CAT IV 600 V, 3000 m CAT III 600 V |
|
Non-operating (storage) |
12,000 m |
||
Over-range |