FLUKE 1555FC
- Stock: Pre-Order
- Model: Insulation Tester 10kV
Key features
·
Quickly configure, start and stop tests on the 1555 remotely, a safe
distance away from any operating, energized equipment, using Fluke
Connect® and a smart phone
·
Real time trending gives you easy-to-see visual cues, rather than hard
to read, rapidly changing values
·
Report creation using Fluke Connect desktop saves time and
makes test results easier to understand
·
Fluke Connect saves test results to the cloud for analysis and
preventive maintenance
Product overview: Fluke
1555 FC 10 kV Insulation Tester
Perform
tests, collect data wirelessly and from a safe distance
The Fluke
1555 insulation resistance tester offers digital insulation testing up to 10
kV, making it ideal for testing high voltage equipment including switchgear,
motors, generators and cables.
Data
collection is easy using the Fluke Connect® wireless app. Remote operation lets
you spend as little time as possible in potentially hazardous zones. Real-time
trending shows a live graph on your phone, rather than a hard-to-read set of
changing values. And you can create reports quickly, using pre-designed
templates that you can customize with company logos. The 1555 insulation tester
can now conduct the entire range of test voltages specified in IEEE 43-2000
with a best in class, CAT IV 600 V safety rating.
Other
useful features:
- Automatic
calculation of Dielectric Absorption (DAR) and Polarization Index (PI)
with no additional setup
- Guard
system eliminates the effect of surface leakage current on high-resistance
measurements
- Selectable
test voltages in 50 V steps from 250 V to 1000 V, and 100 V steps above
1000 V
- CAT
III 1000 V, CAT IV 600 V safety rating
- Warning
function alerts the user that line voltage is present and gives the
voltage reading up to 600 V AC or DC for increased user safety
- Measurements
can be stored in up to 99 memory locations, with each location assigned a
unique, user defined, label for easy recall
- Long
battery life gives the user over 750 tests between charges
- Large
digital/analog LCD for easy viewing
- Capacitance
and leakage current measurement
- Ramp
function for breakdown testing
- Resistance
measurements up to 2 TΩ
- Timer
settings up to 99 minutes for timed tests
Specifications: Fluke 1555
FC 10 kV Insulation Tester
Electrical
Specifications |
||
The
tester's accuracy is specified for one year after calibration at operating
temperatures of 0°C to 35°C. For operating temperatures outside the range
(-20°C to 0°C and 35°C to 50°C), add ±.25% per °C, except on the 20% bands
add ±1% per °C. |
||
Insulation
Resistance Measurement |
||
Test
voltage (DC) |
||
250 V |
Range |
<
250 kΩ, |
Accuracy
(± reading) |
Unspecified |
|
500 V |
Range |
<
500 kΩ |
Accuracy
(± reading) |
Unspecified |
|
1000 V |
Range |
< 1
MΩ |
Accuracy
(± reading) |
Unspecified |
|
2500 V |
Range |
<
2.5 MΩ |
Accuracy
(± reading) |
Unspecified |
|
5000 V |
Range |
< 5
MΩ |
Accuracy
(± reading) |
Unspecified |
|
10000 V |
Range |
< 10
MΩ |
Accuracy
(± reading) |
Unspecified |
|
Bar
graph range |
0 to 1
TΩ (1550C) - 0 to 2 TΩ (1555) |
|
Insulation
test voltage accuracy |
-0%,
+10% at 1 mA load current |
|
Induced
AC mains current rejection |
2 mA
maximum |
|
Charging
rate for capacitive load |
5
seconds per μF |
|
Discharge
rate for capacitive load |
1.5
s/μF |
|
Leakage
current measurement |
Range |
1 nA to
2 mA |
Accuracy |
±(5% +
2 nA) |
|
Capacitance
measurement |
Range |
0.01 μF
to 15.00 μF |
Accuracy |
±(15%
rdg + 0.03 μF) |
|
Timer |
Range |
0 to 99
minutes |
Resolution
setting |
1
minute |
|
Resolution
indication |
1
second |
|
Live
circuit warning |
Warning
range |
30 V to
660 V AC/DC, 50/60 Hz |
Voltage
accuracy |
±(15% +
2 V) |
|
Software
specifications |
FlukeView
Forms™ basic software requires a PC running Windows XP, Windows Vista ,
Windows 7 or Windows 8. |
|
General
Specifications |
||
Display |
75 x
105 mm |
|
Power |
12 V
lead-acid rechargeable battery, Yuasa NP2.8-12 |
|
Charger
Input (AC) |
85 V to
250 V AC 50/60 Hz 20 VA |
|
This
Class II (double insulated) instrument is supplied with a Class 1 (grounded)
power cord. The protective earth terminal (ground pin) is not connected
internally. The extra pin is for added plug retention only. |
||
Dimensions |
269 x
277 x 160 mm (10.6 x 10.9 x 6.3 in) |
|
Weight |
3.7 kg
(8.2 lb) |
|
Temperature
(operating) |
-20°C
to 50°C (-4°F to 122°F) |
|
Temperature
(storage) |
-20°C
to 65°C (-4°F to 149°F) |
|
Humidity |
80% to
31°C decreasing linearly to 50% at 50°C |
|
Altitude |
2000 m |
|
Enclosure
sealing |
IP40 |
|
Input
overload protection |
1000 V
AC |
|
Electromagnetic
compatibility |
EN
61326 |
|
Safety
compliance |
IEC
61010-1: Overvoltage category II, Pollution Degree 2. |