FLUKE 435-II
Pre-Order
FLUKE 435-II
- Stock: Pre-Order
- Model: Three-Phase Power Quality and Energy Analyzer
1,900,000
Features
- Energy loss calculator: Classic active and reactive power measurements, unbalance and harmonic power, are quantified to pinpoint true system energy losses in dollars (other local currencies available)
- Power inverter efficiency: Simultaneously measure AC output power and DC input power for power electronics systems using optional DC clamp
- PowerWave data capture: Captures fast RMS data, show half-cycle and waveforms to characterize electrical system dynamics (generator start-ups, UPS switching etc.)
- Waveform capture: Captures 50/60 cycles (50/60Hz) of each event that is detected in all modes, without set-up
- Automatic Transient Mode: Captures 200 kHz waveform data on all phases simultaneously up to 6 kV
- Fully Class-A compliant: Conducts tests according to the stringent international IEC 61000-4-30 Class-A standard
- Mains signaling: Measures interference from ripple control signals at specific frequencies
- Troubleshoot: Analyze the trends using the cursors and zoom tools
- Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance
- Measure all three phases and neutral: With included four flexible current probes with enhanced thin flex designed to fit into the tightest places
- Automatic Trending: Every measurement is always automatically recorded, without any set-up
- System-Monitor: Ten power quality parameters on one screen according to EN50160 power quality standard
- Logger function: Configure for any test condition with memory for up to 600 parameters at user defined intervals
- View graphs and generate reports: With included analysis software
- Battery life: Up to 8 hours operating time per charge on Li-ion battery pack
- Wireless data download: Download data to PC wirelessly and capture screens using Fluke Connect App
- Measure multiple parameters simultaneously to quickly understand overall power quality health
- View data as simple digital values or more detailed trend graphs that give you fast insight into changes over time, waveforms, and phasor diagrams
- Organize data in tabular format so you can quickly correlate parameters like magnitude, duration, and time to the issues you are experiencing in your facilit
Fluke 435-II Specifications
Volt | |
Vrms (AC + DC) | Measurement range: 1 to 1000 V phase to neutral Resolution: 0.01 V Accuracy: ±0.1% of nominal voltage1 |
Vpk | Measurement range: 1 to 1400 Vpk Resolution: 1 V Accuracy: 5% of nominal voltage |
Voltage Crest Factor (CF) | Measurement range: 1.0 > 2.8 Resolution 0.01 Accuracy: ±5% |
Vrms 1/2 | Resolution: 0.1 V Accuracy: ±0.2% of nominal voltage |
Amps | |
i430-Flex 1x | Measurement range: 5 to 6000 A Resolution: 1 A Accuracy: ±0.5% ±5 counts |
i430-Flex 10x | Measurement range: 0.5 to 600 A Resolution: 0.1 A Accuracy: ±0.5% ±5 counts |
1mV/A 1x | Measurement range: 5 to 2000 A Resolution: 1 A Accuracy: ±0.5% ±5 counts |
1mV/A 10x | Measurement range: 0.5 to 200 A (AC only) Resolution: 0.1 A Accuracy: ±0.5% ±5 counts |
i430-Flex | Measurement range: 8400 Apk Resolution: 1 Arms Accuracy: ±5% |
1mV/A | Measurement range: 5500 Apk Resolution: 1 Arms Accuracy: ±5% |