FLUKE 902 FC
- Stock: Pre-Order
- Model: True-RMS HVAC Clamp Meter
Key Features:
A wireless Fluke Connect®-enabled clamp meter designed
specifically for the needs of HVAC technicians
Offers 200 µA DC current measurements to measure flame rod
Extends resistance range to measure thermistors up to 60kΩ
Captures flue gas temperature
Measures start and run motor capacitors
Measures variable frequency drive performance
Specifications: Fluke 902 FC True-RMS HVAC Clamp Meter
Function: |
||
A ac (via Jaw) |
||
Resolution |
0.1 A |
|
Accuracy |
2.0% ±5 digit (45-65 Hz) |
|
2.5% ±5 digit (65-400 Hz) |
||
Range |
600.0 A |
|
Crest Factor (50Hz or 60Hz) |
2.5 MIN@220 A |
|
V ac |
||
Resolution |
0.1 V |
|
Accuracy |
1.5% ±5 digits |
|
Range |
600.0 V |
|
V dc |
||
Resolution |
0.1 V |
|
Accuracy |
1.5% ±5 digits |
|
Range |
600.0 V |
|
Ohms |
||
Resolution |
0.1/1/10 |
|
Accuracy |
1% ±5 digits |
|
Range |
600/6000/60.00 kΩ |
|
Capacitance |
||
Resolution |
0.1/1 µF |
|
Accuracy |
1% ±4 digits |
|
Range |
100.0/1000 µF |
|
µA |
||
Resolution |
0.1 µA |
|
Accuracy |
1% ±5 digits |
|
Range |
200 µA |
|
Contact temperature |
||
Resolution |
0.1 C/F |
|
Accuracy |
1% ±8 digits |
|
Range |
-40 to 400 °C (-40 °F to 752 °F) |
|
Continuity beeper |
||
Beeper volume |
75 dBA nom. 15 cm. from case front |
|
On threshold |
<=30 Ω |
|
Mechanical and General Specifications: |
||
Maximum voltage between any terminal and earth ground |
600 V |
|
Battery type |
2 AA alkaline batteries, NEDA 15A, IEC LR6 |
|
Temperature |
Operating: -10 °C to +50 °C (14 °F to +122 °F) |
|
Operating humidity |
Non condensing (< 10 °C [50 °F]), ≤90 % RH (at 10 °C to
30 °C [50 °F to 86 °F]), ≤75 % RH (at 30 °C to 40 °C (86 °F to 104 °F)), ≤45
% RH (at 40 °C to 50 °C (104 °F to 122 °F)) |
|
Altitude |
Operating: 3,000 m (9,842 ft) |
|
Dimensions |
230 x 83.7 x 45.4mm (9.06 x 3.30 x 1.39 in) |
|
Weight (meter only) |
419 g (15 oz) |
|
Safety |
IEC 61010-1, Pollution Degree 2 |
|
IP Rating |
IEC 60529: IP30, non-operating |
|
Radio Frequency Certification |
FCC ID:T68-FBLE IC:6627A-FBLE |
|
Electromagnetic Compatibility (EMC) |
International: IEC 61326-1: Portable, Electromagnetic
Environment, IEC 61326-2-2 CISPR 11: Group 1, Class A Korea (KCC): Class A
Equipment (Industrial Broadcasting & Communication Equipment) USA (FCC):
47 CFR 15 subpart B. This product is considered an exempt device per clause
15.103. |
|
Temperature coefficients |
Add 0.1 × specified accuracy for each degree C above 28 °C
or below 18 °C |