Main Menu / Categories
Your Cart

FLUKE 1630-2 FC

FLUKE 1630-2 FC
Pre-Order
FLUKE 1630-2 FC
  • Stock: Pre-Order
  • Model: Earth Ground Clamp
597,500
No Shipping Charges

Product overview: Fluke 1630-2 FC Earth Ground Clamp

The 1630-2 FC clamp measures earth ground loop resistances for multi-grounded systems using the dual-clamp jaw. This test technique eliminates the dangerous and time-consuming activity of disconnecting parallel grounds, as well as the process of finding suitable locations for auxiliary test stakes. You can also perform ground tests in places that were previously difficult: inside buildings, on power pylons or anywhere you don't have access to soil to place auxiliary test stakes.

Earth ground ac leakage current measurement

  • Identify ac leakage currents without disconnecting the earth ground stake from the grounding system–ideal for system troubleshooting.
  • Rugged heavy-duty clamp jaw stays in alignment and in calibration even in every day, on-the-job industrial environments.

Logging measurements

  • The earth ground clamp saves time by automatically recording data at pre-set intervals
  • Saves up to 32,760 measurements in memory at the set logging interval.
  • Saves time by recording and storing measured values.

    Specifications: Fluke 1630-2 FC Earth Ground Clamp

    Electrical Specifications
    Maximum voltage to earth ground1000 V
    Battery typeAA alkaline IEC/EN LR6 (x4)
    Battery lifeMore than 15 hours*
    * In Ground Resistance measurement mode, with backlight turned off, and RF mode turned off
    Frequency range40 Hz to 1 kHz
    Ingress protectionIEC/EN 60529: IP30 with jaw closed
    LCDDigital reading9999 counts
    Refresh rate4 per second
    Operating temperature-10 °C to + 50 °C 
    Storage temperature-20 °C to + 60 °C
    Operating humidityNon condensing (<10 °C) (< 50 °F)  
    ≤90% RH (at 10 °C to 30 °C [50 °F to 86 °F])
    ≤75% RH (at 30 °C to 40 °C [86 °F to 104 °F]) 
    ≤45% RH (at 40 °C to 50 °C [104 °F to 122 °F])
    (Non condensing)
    Operating altitude2000 m (6561 feet)
    Storage altitude12 000 m (39,370 feet)
    Reference temperature23 °C ±5 °C (73 °F ±9 °F)
    Temperature coefficient0.15% x (specified accuracy)/ °C (<18 °C or >28 °C [<64.4 °F or >82.4 °F])
    Overload indicationOL
    Data logging capacityMinimum of 32,760 measurements
    Data logging interval1 second to 59 minutes and 59 seconds
    Display reading specification with standard loop resistance
    Input (Ω)MinimumMaximum
    0.4740.4170.531
    0.50.4430.558
    109.5510.45
    10096104
    Safety
    GeneralIEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1
    MeasurementIEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 V
    Current clamp for leakage current measurementsIEC/EN 61557-13: Class 2, ≤30 A/m
    Resistance to earthIEC/EN 61557-5
    Effectiveness of thepProtective measuresIEC/EN 61557-16
    Electromagnetic compatibility (EMC)InternationalIEC/EN 61326-1: Portable Electromagnetic Environment
    CISPR 11: Group 1, Class B, IEC/EN 61326-2-2
    Korea (KCC)Class A equipment (Industrial Broadcast & Communications Equipment)
    USA (FCC)47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
    Wireless Radio
    Frequency range2412 MHz to 2462 MHz
    Output power<10 mW
    Radio frequency certificationFCC ID:T68-FBLE IC:6627A-FBLE
    General Specifications
    Conductor size40 mm (1.57 in) approximately
    Dimensions (L x W x H)283 x 105 x 48 mm (11.1 x 4.1 x 1.9 in)
    Weight880g (31 oz)
    WarrantyOne year
    Earth Ground Loop Resistance
    RangeAccuracy1  ± (% of reading + Ω)
    0.025 Ω to 0.249 Ω1.5% + 0.02 Ω
    0.250 Ω to 0.999 Ω1.5% + 0.05 Ω
    1.000 Ω to 9.999 Ω1.5% + 0.10 Ω
    10.00 Ω to 49.99 Ω1.5% + 0.30 Ω
    50.00 Ω to 99.99 Ω1.5% + 0.50 Ω
    100.0 Ω to 199.9 Ω3.0% + 1.0 Ω
    200.0 Ω to 399.9 Ω5.0% + 5.0 Ω
    400 Ω to 599 Ω10.0% + 10 Ω
    600 Ω to 1500 Ω20.00%
    1  Loop resistance with no inductance, conductor centered and perpendicular to jaw
    Earth ground leakage current mA
    Autorange 50/60 Hz, True rms, crest factor CF ≤3
    RangeResolutionAccuracy1  ± (% of reading + mA)
    0.200 mA to 3.999 mA1 μA2.0% + 0.05 mA
    4.00 mA to 39.99 mA10 μA2.0% + 0.03 mA
    40.0 mA to 399.9 mA100 μA2.0% + 0.3 mA
    0.400 A to 3.999 A1 mA2.0% + 3 mA
    4.00 A to 39.99 A10 mA2.0% + 30 mA
    1 Applies to signal frequency
    • 40 Hz to 1 kHz with filter set to OFF
    • 40 Hz to 70 Hz with filter se to ON