ES1010 FUZRR




- Stock: Pre-Order
- Model: Wireless H/L Voltage Current Ratio Tester
Tester | High voltage detector | Mainframe (current clamp) |
Range | 0.0mA~1200A(50/60Hz Auto) | 0.0mA~20A |
Resolution | 0.1mA | 0.1mA |
Jaw size | φ50mm | φ7.5mm |
Accuracy | ±2%±5dgt | ±0.5%±5dgt |
Sampling Rate | 2 times/second | |
Function | High-low voltage current transformer primary and
secondary loop current, transformation ratio, polarity, phase, and on-line
test; current and voltage ratio on both sides of transformer; on-line test;
load current test | |
Transmission type | Wireless transmission, linear transmission distance 30m | |
Change gear | Fully automatic shift | |
Power | DC6V 7# alkaline battery(1.5V AAA×4) | DC7.5V 5# alkaline battery(1.5V LR6×5) |
Test method | Clamp CT | |
Dimensions | W/T/H 87*37*262mm | Host:W/T/H 100*35*204mm |
| | Current clamp:W/T/H 42*20*137mm |
Display mode | LCD:128dots×64dots Blue screen backlight for dim
places | |
LCD Size | 62mm×44mm | |
Change ratio | Three kinds of transformation ratio display: (The primary
and secondary circuit actually measured the current transformation ratio; the
conversion ratio of the secondary circuit 5A; 10kV-YY transformer conversion
ratio of 10kV/380V), the maximum ratio of 1:1 million | |
Line voltage | Line test with insulation sheath below 60kV or bare wire
current test below 35kV (with insulation rod operation) | |
Lead length | Current clamp lead 2 meters | |
Weight | Total instrument weight:7Kg(Insulated rod and instrument
package) | |
| High pressure detector:370g(Including battery) | |
| Host:409g(Including battery) | |
| Current clamp:180g | |
Data interface | USB transmission | |
Overflow display | Over-range overflow function: “OL A” symbol display | |
Data storage | 500 groups, press MENU to keep data, HOLD symbol
display, press MENU again to cancel | |
Data review | Long press the MENU button to enter the data
reference mode, MR symbol display, press MENU again
to exit | |
Data is full | Data full function: “FULL” symbol display | |
Switch display mode | Long press the POWER button to switch between
the test display mode and the conversion ratio display mode | |
No signal indication | When the host does not receive the transmit signal, it
prompts “no signal” | |
Automatic shut-down | About 15 minutes after power on, the meter will
automatically shut down | |
Battery voltage | When the battery voltage drops to 3.5V, the low-power
indicator lights to remind you to replace the battery | When the battery voltage drops to 5.2V, the battery voltage
is low symbol to remind to replace the battery |
Insulation rod | Five section insulation rod (5 meters) | |
Insulation strength | AC 60kV/rms | |
Line test | Insulation sheath wire test below 60kV line voltage, bare
wire test below 60kV (with insulation rod operation) | |
Working temperature | -10℃~40℃ | |
Storage temperature | -10℃~60℃ | |
Relative humidity | 0℃~31℃≦75%,31℃~40℃≦50% | |
Suitable for safety regulations | IEC1010-1、IEC1010-2-032、Pollution degree 2、CAT Ⅲ(600V)
IEC61326(EMC standard) | |