FR2000A+ FUZRR
- Stock: Pre-Order
- Model: Digital Clamp On Ground Earth Resistance Tester
·
Resistor Resolution:0.001Ω
·
Current resolution:0.01mA
·
Measurement Method: mutual inductance
·
Data Storage:300 groups, "MEM" storage
indication, displaying "FULL" symbol means the storage is full
·
Measure Time:2 times/sec
Model |
Resistance Range |
Current Range |
FR2000A+ |
0.01Ω-200Ω |
— |
FR2000+ |
0.01Ω- 500Ω |
— |
FR2000C+ |
0.01Ω-1200Ω |
0.00mA-20A |
FR2000B+Explosion-proof |
0.01Ω-1200Ω |
TECHNICAL PARAMETERS
Function |
Ground resistance test, loop resistance test, leakage
current test |
Ambient Temperature and Humidity |
23℃±5℃,
below 75%rh |
Power Supply |
DC 6V (4 AA dry batteries) |
Measurement Method |
mutual inductance |
Resistor Resolution |
0.001Ω |
*Current resolution |
0.01mA |
Jaw size |
55mm×32mm |
*Ω + A sync display |
Ω + A sync display |
Ground voltage measurement function |
None |
Display Mode |
4-digit LCD display, black screen design |
LCD size |
46mm×29mm |
Meter size |
Length, width and height:285mm×85mm×58mm |
Measure Time |
2 times/sec |
Data Storage |
300 groups, “MEM” storage indication, displaying “FULL”
symbol means the storage is full |
Data Access |
“MR” symbol indication when viewing data |
Overflow Display |
“OL” symbol indication when over range overflow |
Interference Test |
Automatically identify interference signals, and the
“NOISE” symbol indicates when the interference current is large |
Alarm Function |
When the measured value exceeds the alarm setting value,
an alarm prompt will be issued |
Battery Voltage |
Real-time display of battery power, reminding to charge in
time when the battery voltage is low |
Automatic shut-down |
Automatic shutdown after 5 minutes of startup |
Power consumption |
50mA Max |
Quality |
Meter: 1180g (including battery) |
Working temperature and humidity |
-10℃~40℃; below 80%rh |
Storage temperature and humidity |
-20℃~60℃; below 70%rh |
Insulation resistance |
Above 20MΩ (500V between circuit and case) |
Pressure resistance |
AC 3700V/rms (between circuit and case) |
External Magnetic Field |
<40A/m |
External Electric Field |
<1V/m |
Suitable for safety regulations |
IEC61010-1 (CAT III 300V, CAT IV 150V, pollution degree
2); IEC61010-031; IEC61557-1 (grounding resistance) |